Dual-transformer Rc/Rh systems: choosing the C wire that powers Mysa
Last updated: October 5, 2026
Purpose
Use this article when a customer has one Mysa thermostat controlling equipment powered by two separate 24 V transformers, such as hydronic in-floor heat on Rh/W and ducted air conditioning on Rc/Y/G.
Key rule
In a dual-transformer setup, do not tie the two transformer circuits together. The Rh and Rc circuits must remain isolated, and only one transformer common should be connected to Mysa’s C terminal.
Mysa is flexible: the thermostat can be powered from either the heating transformer or the cooling transformer. Which transformer powers Mysa depends on which transformer the connected C wire returns to.
How Mysa is powered
Option A: Cooling transformer powers Mysa
Use this when the cooling transformer feeding Rc has enough spare capacity for Mysa’s approximate 3 VA load and there is an available C wire returning to the cooling transformer.
Rcpowers the thermostat through the connected cooling-sideC.Rcalso powers cooling/fan calls such asY1,Y2, andG.Rhis not powering the thermostat in this wiring arrangement; it only feeds heating calls such asW1andW2.There is no
Creturn path forRhin this arrangement.
Option B: Heating transformer powers Mysa
Use this when a C wire is available back to the heating transformer, such as a hydronic system with R, W, and C at the thermostat location.
Rhpowers the thermostat through the connected heating-sideC.Rhalso powers heating calls such asW1andW2.Rconly powers cooling/fan calls such asY1,Y2, andG.
Important: connect only one C wire
If both systems provide a common wire, connect only one C wire to Mysa: either the heating-side C or the cooling-side C. Cap off and safely isolate the unused C wire. Do not connect both commons together at the thermostat.
Backplate/jumper guidance
For two-transformer systems, ensure the backplate jumper/switch is set to keep Rh and Rc isolated. Use the dual-transformer / separated Rh-Rc position shown in the Mysa installation materials.
Transformer capacity
Mysa adds approximately 3 VA of load to whichever transformer is connected to C.
If Mysa is powered from the heating transformer, add this load to the hydronic/heating transformer capacity calculation.
If Mysa is powered from the cooling transformer, add this load to the cooling transformer capacity calculation.
If several Mysa thermostats are already powered by the same hydronic transformer, confirm the transformer has enough capacity. Upgrade the transformer or add an approved dedicated auxiliary transformer if total load exceeds available VA.
Example: hydronic heat plus ducted AC
Customer has three hydronic wires at the thermostat: R, W, and C, plus separate cooling wires from a ducted AC system.
Connect hydronic
RtoRh.Connect hydronic
WtoW1.Connect hydronic
CtoCif choosing the heating transformer to power Mysa.Connect cooling power to
Rc.Connect cooling/fan control wires to the applicable cooling terminals, such as
Y1,Y2, and/orG.If the cooling system also has a
Cwire at the wall, cap it off and leave it unused when the hydronicCis connected.
Support response guidance
When replying to a customer, avoid saying Mysa must always draw power from either cooling or heating. The accurate answer is:
Mysa can be powered by either transformer in a dual-transformer setup. The transformer connected to the C wire used at Mysa is the transformer that powers the thermostat. The other transformer remains isolated and only powers its own call circuits.
When to escalate
The customer is unsure which transformer a
Cwire returns to.Both
Cwires have already been tied together.The system uses non-standard controls, zone boards, or relay panels.
The transformer VA capacity is unknown or appears insufficient.
The installation is for a VIP/customer-sensitive retrofit and needs human wiring confirmation.