Use this guide when: a newly installed Mysa LV or low-voltage thermostat is dead/no display, loses power after initially powering up, or the customer reports there is no 24V power at the thermostat.
Safety first
Have the customer turn power off at the breaker before touching wiring or opening the furnace cabinet.
Do not have the customer bypass any furnace safety switch, door interlock, float switch, fuse, or other safety device.
If they are not comfortable checking the furnace cabinet or using a multimeter, advise them to contact an HVAC technician.
Quick diagnosis
If the Mysa is dead, the furnace control board has no status LED, and there is no 24V at R/C, the issue is usually upstream of the thermostat: no 120V to the furnace, an open safety/interlock, a tripped high-limit or float switch, or a blown low-voltage fuse.
Troubleshooting steps
Confirm the furnace has line power. Ask whether the furnace service switch/breaker is on. If the control board has no LED at all, suspect no 120V to the furnace or an open safety circuit.
Confirm the blower/furnace door is fully seated. Many furnaces have a door interlock switch. If the door is open or not seated, it can interrupt 120V to the furnace and remove 24V power from the thermostat.
Check the furnace diagnostic LED. If everything is normal, many boards show a steady or slow green status LED. Record any diagnostic flash code before resetting power.
Check the low-voltage fuse. Inspect the board fuse, often a purple 3A automotive-style fuse. Replace only with the same rating if blown. If it blows again, stop and escalate to HVAC/electrician because there may be a short.
Measure 24V at the furnace board. With the furnace powered and cabinet secured, verify ~24VAC between R and C. If no 24V is present at the board, the thermostat cannot power up.
Check for safety switches that can interrupt 24V. If present, verify the condensate pump/float switch is not tripped. Also consider whether the furnace tripped on high limit, which can interrupt 24V to the thermostat.
Check airflow causes if high limit is suspected. Ask the customer to confirm the air filter is clean and installed correctly. A dusty control board or restricted airflow can point to furnace maintenance issues.
Confirm wiring matches the system. For systems with AC, expect cooling wires at Y and C on the furnace board. On Mysa LV, the yellow cooling call wire should be connected to Y1. If the system is heat-only, confirm no unused or incorrect Y/Y2 wiring is creating confusion.
Confirm setup code/configuration. If the device powers but heat does not run, confirm the correct setup code was entered for the system type. A missing or incorrect code can prevent the furnace from calling heat even when wiring is otherwise correct.
Key notes
There should be no delay for Mysa to power up once proper 24V power is present.
Swapping to an alternate C wire can help rule out a damaged conductor, but only after confirming furnace power, door interlock, fuse, and 24V at the board.
If the furnace board has no LED, do not assume the thermostat is defective. First verify furnace power, door interlock, low-voltage fuse, and any condensate/high-limit safety interruptions.
When to replace the Mysa
Do not replace the device until the above checks confirm the furnace is providing stable 24V at R/C and the Mysa still does not power up. If 24V is missing at the furnace or interrupted by a safety condition, the root cause is furnace-side and should be resolved before sending a replacement.
Escalation path
If the fuse is blown repeatedly, escalate to HVAC/electrician for a short investigation.
If there is no furnace board LED and the breaker/switch/door appear correct, escalate to HVAC to verify 120V and furnace board power.
If 24V is present at the board but not at the thermostat, investigate the thermostat cable/conductor path.
If 24V is present at the thermostat and Mysa remains dead, proceed with replacement review.