Error Codes — Mysa for In-Floor Heating
Last updated: July 6, 2026
If your Mysa for In-Floor Heating displays an error code, use this guide to identify the issue and resolve it.
Error Code Reference
Code | Meaning | Cause |
|---|---|---|
H2 | Open heating circuit | No heater load detected |
H3 | GFCI trip | Ground fault detected |
I3 | Floor sensor issue | Sensor loose, disconnected, or out of range |
H2 — Open Heating Circuit
The thermostat detects no heater load on the circuit.
Possible causes:
Heating mat not connected
Loose wire connection
Damaged heating element
How to fix:
Turn off power at the breaker
Check that the heating mat wires are securely connected to the LOAD terminals
Verify the heating mat is not damaged
Restore power and test
Warning Turn off power at the breaker before checking any wiring connections.
H3 — GFCI Trip
The built-in GFCI detected a ground fault and tripped for safety.
Possible causes:
Ground fault in the heating mat
Moisture in the electrical connections
Damaged wiring
How to fix:
Press the Reset button on the side of the thermostat
If it trips again immediately, there may be a ground fault in the system
Check for moisture or damage in connections
Contact an electrician if the issue persists
Caution Repeated GFCI trips indicate a potential electrical fault. Do not bypass the GFCI. Have the system inspected by a qualified electrician.
I3 — Floor Sensor Issue
The floor sensor is not reading correctly.
Possible causes:
Sensor wire disconnected
Sensor damaged or broken
Sensor resistance outside the 5K–40K Ohm range
How to fix:
Turn off power at the breaker
Check that the floor sensor wires are connected to the sensor terminals
Verify the sensor wire is not damaged
If using an existing sensor, confirm it's within the 5K–40K Ohm range
Recalibrate the sensor in app settings if needed
Tip If you installed a backup sensor during initial setup, you can switch to it without needing to access the floor.